RTD PT-100 to V/I Converter

RTD PT-100 sensors are widely used in temperature measurement applications in the range -100 to +500 oC. The SIM µ 2.0 RTD Conditioning & Isolation modules offer a perfect interface between the field mounted RTD sensor & the PLC/DCS system used for measurement and control application.

The SIM µ 2.0 RTD interface modules have In-built RTD Non-Linearity compensation circuit, which results in corrected non-linearity error less than 0.4% over the entire PT-100 measurement range of -200 to+850°C. The In-built Cable Resistance Compensation feature helps in avoiding errors due to resistance of the connecting wire when the RTD is connected in 3-Wire configuration. Cable lengths in excess of 100 meters can be used without introducing error in the measurement.

Ordering Information

Isolation (I) Input Type Output Type Supply I/P Signal Range O/P Signal Range Isolation
I I/P O/P Supply X XX 3P
I

LRTD

V

I

2D

-200 – +850°C *:X 0-5V:05

0-10V:10

4-20mA:42

0-20mA:20

3P

*: Max. Measurement Range
X: Actual RTD PT-100 Range

Frequent Searches for RTD Temperature Transmitter

Temperature Transmitter India, RTD Transmitter Pune, RTD Temperature Transmitter New Delhi, Temperature Transmitter Bangalore, RTD Transmitter Mumbai, RTD Temperature Transmitter Chennai, RTD Temperature Transmitter India, Temperature Transmitter Kolkata, RTD Transmitter Hyderabad, RTD Temperature Transmitter Ahmedabad, RTD Temperature Transmitter Nashik

Download PDF

  • Input : RTD PT-100 (3 Wire)
  • RTD Non-Linearity compensation: In built.
  • Error < 0.4%
  • Cable Resistance Compensation: In built.
  • Max. Length of Cable: 100m (Cable Resistance<25 Ohm).
  • Energy Efficient Module.
  • Low Noise & Low drift for long term stability.
  • Response Time < 500mSec.
  • 2kv 3 Port Isolation.

Applications

  • Heating Control System
  • Boiler Temp. Control System
  • Motor Winding Temperature monitoring systems
  • Data Acquisition Systems

Download PDF

 

Input Signal RTD (PT-100,3Wire) Input Options: (-200 to +850°C)*
*: Max. Measurement Range
Factory Set
Input Impedance For RTD (PT-100) 100K Ohm
Output Signal Output Options:0- 5VDC, 0-10VDC, 0-20mA, 4-20mA. Factory Set
Load Resistance For Output Voltage >1 k Ohm
For Output Current < 500 Ohm
Performance Accuracy ±0.5% of Span
Linearity 0.2%
Temperature Drift 0.01% / °C
Response Time < 500mSec
Calibration Zero & Span (Trimpot )

Download PDF

 

Isolation 2KV – 3 Port.
Power Supply Voltage 24VDC(nominal)
Operating Range 18 to 36 VDC
Ripple <  100mVpp
Power Supply Current 150mA Max.
Enclosure ABS Plastic, 35 mm DIN Rail Mounted. IP40 Protection class. Output Single W – 22.5mm
H – 75mm
D – 110mm
Operating temp. range 0 – 55°C
Storage temp. range 0 – 80°C
Relative Humidity 0 – 90%
RH Non-Condensing
Max. Altitude 3000 mts above MSL

Download PDF

Single input & Single output Converter

RTD PT-100 to Voltage & Current Converter

Pin Details Pin Details
1 +Input 5 +Output
2 -Input 6 -Output
3 -Input 7 +24VDC
4 NC 8 GND

Download PDF

Additional information

Input Types

RTD Pt-100 Sensor

Output Signal

Current 0-20/4-20mA (4 Wire), DC Voltage (+/-10V)

Supply

24VDC

Isolation Level

2 KV

Enclosure

ABS Plastic

Product Type

Converter