Powerline Transducers – AC Voltage & Current Converter 24VDC Supply

The AC Voltage and AC Current Transducers find extensive use in monitoring Powerline parameters. The SIM µ 2.0 Powerline Transducers interface with AC voltage (e.g. 0-100/300/500 V) & AC Current (CT signals: 0-1A, 0-5A) inputs to provide isolated 0-10V/4-20mA DC output that is linearly proportional to the RMS value of the 50/60Hz AC input.

The Isolation between I/P & O/P (2KV) allows measurement in the presence of High Common mode voltages at the input while ensuring safety of the measuring equipment.

Ordering Information

Isolation (I) Input Type Output Type Supply 24VDC (2D) I/P Signal Range O/P Signal Range Isolation No of O/P For Dual
I I/P O/P Supply XX X 3P xx
I Iac

 

Vac

Vdc

 

Idc

2D

0-1A:01 0-5V:05

0-10V:10

4-20mA:42

0-20mA:20

3P 121
0-5A:05
0-8A:08
0-100V:100
0-300V:300
0-500V:500

Note: 12I extension implies Single Input & Dual Isolated output.

 

Download PDF

  • Input : AC Current, AC Voltage.
  • Output : 0-10V/4-20mA
  • Low Noise & Low drift for long term stability.
  • Response Time < 150mSec.
  • 2kV 3 Port Isolation.
  • Performance guaranteed from 0-55°C.
  • Dual isolated outputs

Note: The width and termination details of Single /Dual output type units may vary depending on input specifications due to internal space requirements.

Applications

  • AC/DC Drive systems
  • PLC Systems
  • Data Acquisition Systems

Download PDF

 

AC Input Voltage Signal Input Options: 0- 100VAC,0-300VAC,0-500VAC. Factory Set
AC Input Current Signal (From CT) 0-1A AC,0-5A AC,0-8A AC. Factory Set
C.T Burden <0.5VA
Input Impedance For Voltage >1M Ohm
DC Output Signal Output Options: 0- +5VDC, 0- +10VDC, 1-5VDC, 0-20mADC, 4-20mADC. Factory Set
No of Outputs Two (Max)
Load Resistance For Output Voltage >1 k Ohm
For Output Current < 500 Ohm
Performance Accuracy ±0.5% of Span
Linearity 0.2%
Temperature Drift 0.01% / °C
Response Time < 150mSec
Calibration Zero & Span (Trimpot )

Download PDF

Isolation 2KV – 3 Port.
Power Supply 24VDC
Operating Voltage 18-36VDC
Ripple <100mVpp
Current 200mA Max.
Enclosure ABS Plastic, 35 mm DIN Rail Mounted. IP40 Protection class. Single Output W – 22.5mm or 55mm
H – 75mm
D – 110mm
Dual output W – 55mm or 100mm
H – 75mm
D – 110mm
Operating temp. range 0 – 55°C
Storage temp. range 0 – 80°C
Relative Humidity 0 – 90%
RH Non-Condensing
Max. Altitude 3000 mts above MSL

 

Download PDF

Single input & Single output Converter

Single input & Single output Converter

Pin Details Pin Details
1 NC 5 +Output
2 ~Input 6 -Output
3 ~Input 7 +24Vdc
4 NC 8 GND
Single input & Dual output Converter

Single input & Dual output Converter

Pin Details Pin Details
1 NC 11 GND
2 ~Input 12 GND
3 ~Input 13 +24VDC(Supply)
4 NC 14 +24VDC(Supply)
5 NC 15 NC
6 NC 16 – Output2
7 NC 17 +Output2
8 NC 18 NC
9 NC 19 -Output1
10 NC 20-38 +Output1

 

Download PDF

Additional information

Input Types

AC Current, AC Voltage

Output Signal

Current 0-20/4-20mA (4 Wire), DC Voltage (+/-10V)

Supply

24VDC

Isolation Level

2 KV

Enclosure

ABS Plastic

Product Type

Converter

Reviews

There are no reviews yet.

Be the first to review “Powerline Transducers – AC Voltage & Current Converter 24VDC Supply”

Your email address will not be published. Required fields are marked *

Translate »