Analog Signal Conditioning and Isolation (5 KV)

Designed to isolate and condition analog signal conditioners by Canopus Instruments are the best available in the market. The analog signal conditioners manipulate the analog signal in such a way that it prepares the device for the next stage.

Download PDF

Analog measurements in High Voltage Systems, where operating voltages exist in the range of 1KVolts to 2KVolts, require higher isolation levels to be maintained in the Signal Isolators in order to meet the safety standards. The 5KVolt isolated Signal Conditioning modules are specially designed to meet these specifications.

3 Port 5KV isolation is achieved by careful selection of design parameters and components used in the product. Each unit is individually subjected to 5KV isolation test in our factory, to ensure compliance with the required specifications.

Ordering Information

Isolation (I) Input Type Output Type Supply I/P Signal Range O/P Signal Range Isolation Level
I I/P O/P

Supply

X XX 5KV
I

mV

V

I

V

I

90-27VAC:FU

0-100mv:100 0- ±5V:5

0-±10V:10

04-20mA:42

5KV
0-500mV:500
0-10V:10
0-100V:100
4-20mA:42

Frequent Searches for Analog Signal Conditioning and Isolation

Analog Signal Conditioning India, Analog Signal Isolators Pune, Analog Signal Converters Mumbai, Analog Signal Conditioners Bangalore, Analog Signal Isolators Hyderabad, Analog Signal Converters New Delhi, Analog Signal Conditioners Ahmedabad, Analog Signal Conditioners Nashik, Analog Signal Converters Kolkata
Download PDF

  • Input option: mV (100mV up to 1000mV), V (10v up to1000V).
  • Output Option: ±5V, ±10V.
  • Universal Power Supply
    Response Time < 1mSec.
  • Low Noise & Low drift for long term stability.
  • Performance guaranteed from 0-55 0C.
  • 5kv 3 Port Isolation.

 

Download PDF

DC Input Signal Input Options:
mV(±100mV upto ±1000mV),
V(±10V upto ±1000V)
0-20mA, 4-20mA
Factory Set.
Input Impedance For mV:
For Voltage
For Current
1M Ohms
>100K Ohms
100 Ohms
Output Signal Output Options:
±5VDC or ±10VDC
4-20mADC
Factory Set.
Load Resistance across O/P
Voltage O/PCurrent O/P
>1K Ohms

<500 Ohms

Performance Accuracy ±0.2% of Full scale at 25°C
Linearity ±0.1% of Span
Response Time <1 m Sec
Calibration Zero & Span (Trimpot )

 

Download PDF

Isolation 5KV – 3 Port.
Leakage Current <5mA
Power Supply Voltage 90-270VAC,50Hz
Enclosure
ABS Plastic, 35 mm DIN Rail Mounted. IP40 Protection class.
Single Output W – 100mm
H – 75mm
D – 110mm
Terminals Mechanical Screw ON terminals with 1.5 Sq.mm wire size provided for both supply & signal.
Operating temp. range 0 – 550C
Storage temp. range 0 – 800C
Relative Humidity 0– 90%
RH Non-Condensing
Max. Altitude 3000 mts above MSL

 

Download PDF

Mechanical Dimensions

Single input & Single output Converter

isolation-level-5kv-mechanical-details

Pin Details Pin Details
1 +Input 11 NC
2 -Input 12 NC
3 NC 13 NC
4 NC 14 NC
5 NC 15 NC
6 NC 16 NC
7 NC 17 90-270VAC
8 NC 18 Neutral
9 +Output 19 Earth
10 -Output 20 NC

 

Download PDF

Additional information

Isolation Level

5 KV

Enclosure

ABS Plastic

Product Type

Isolator

Reviews

There are no reviews yet.